Usages:
PGJI low voltage non-power auto compensation cabinet is suitable for
triphase AC power voltage 380V , 50HZ electric distribution system
of industrial & mineral enterprises , plants and civil houses
, which are used to increase the power factor of the electric net
and reduce the expenditure of the electric distribution system and
the transformers .
The Main Technology Parameter of Compensation Cabinet
1. Complied with the IEC Standard
2. Normal power voltage is AC400V 50Hz
3. Normal capability 75KVAR-300KVARBe (dividable automatically )
4. With the protection of the capacitor single misphasing short circle
.The misphasing capability is 30KA
5. With the protection of the over power voltage and the figure is
during 400 to 440V as well as zinc oxide arrester absorbing system
.
6.When the normal power current is more than 1.3 times of the capacitor
.It can cut the capacitor safely .
7.Install the current limiting reactor to limit the current under
50 times of the normal current of the capacitor when it is in the
stage of the switch shut off .
8. The capacitor is circularly cut in equal share. The extended time
is between 10S TO 120S adjustable .
9. The discharge installation of the capacity is the power voltage
£¼50V after the discharge 10S .
PGJ 1 Capacitance Compensation Cabinet Interior Structure -Front
|

PGJ 1 Capacitance Compensation Cabinet
Interior Structure -Rear |
|
|
 |
The
Main Technology Parameter of Compensation Cabinet
1. Complied with the IEC Standard
2. Normal power voltage is AC400V 50Hz
3£®Normal capability 75KVAR-300KVAR(Be dividable automatically
)
4£® With the protection of the capacitor single misphasing short
circle .The misphasing capability is 30KA .
5£®With the protection of the over power voltage and the figure
is during 400 to 440V as well as zinc oxide arrester absorbing
system .
6£®When the normal power current is more than 1.3 times of the
capacitor .It can cut the capacitor safely .
7. Install the current limiting reactor to limit the current
under 50 times of the normal current of the capacitor when it
is in the stage of the switch shut off .
8. The capacitor is circularly cut in equal share. The extended
time is between 10S TO 120S adjustable .
9. The discharge installation of the capacity is the power voltage
£¼50V after the discharge 10S .
|
Installation
Manual for PGJ1 Capacitance Compensation Cabinet
 |
 |
|
|