Description
|
Unit
|
Data
|
|
Rated
Voltage
|
kV
|
12
|
|
Rated
Frequency
|
Hz
|
50
|
|
Main
Generatrix Rated Current
|
A
|
630
|
|
Main
Generatrix , Grounded Circuit Rated Short time Tolerant
Current
|
kA/S
|
25/3
|
|
Main
Return , Grounded Circuit Rated Peak Value Tolerant
Current
|
kA
|
50
|
|
Main
Return , Grounded Circuit Rated Short Circuit On &off
Current
|
kA
|
50
|
|
Over
Load Switch Full Capability Break Times
|
´Î
|
100
|
|
Fusible
Cutout Dropout Current
|
kA
|
31.5
|
|
Machine
Life
|
CE
|
1000
|
|
1min
Alternate with Power Frequency Withstand Voltage (With
Figure), Insulated the Breakpoint from the ground
|
kV
|
42/48
|
|
Alternated
with Thunder Semi-impact Withstand Voltage (Data) ,
Insulated the Breakpoint from the ground
|
kV
|
75/85
|
|
Two
times Return 1 min Power Frequency Standing Voltage
|
kV
|
2
|